NPBHZA03

 

Feature

² Outdoor using, protection level IP55, anti rain, dust, sun, rust, corrosion.

² Cabinet outside-size: 2100*900*900mm(not including air-conditioner), internal space 38U.

² Environment and power controller contains input/output power voltage and current monitoring, smoke detector, water detector, door detector, temperature/humidity detector, air-conditional monitoring and control, monitoring and so on.  

² Input power module contains circuit-breaker, AC arrester and emergency diesel generator interface.

² Provide 2 LED illumination when door open.

² Provide a network camera for cabinet internal monitoring.

² Supports platform software, supports maps, multiple sets of device networking, remote control, alarm management, operational dimension, statistical analysis, etc.

Hardware specification

Item


Cabinet Specification

Cabinet

Cabinet size

Outside size: 2100*900*900mm(not including air-conditioner)

Cabinet material

SGCC, EPS anti-fire material inside.

Internal space

38U

Environment and power controller

Dimension

420*280*44mm, 1U rack mounted

Power input

AC100-240V, 50/60Hz

AC output

2 channels, on/off remote controlled, detect voltage and current

DC12V output

8 channels, on/off remote controlled, detect voltage and current

Power supply for smoke detector, camera and so on.

Electronic lock interface

2 channels, Control electronic-lock unlock

RS485

8 channels standard RS485

RS232

1 channels standard RS232

DI(digital signal input)

Dry-connector type, 5 channels, device like smoke detector, door detector signal input

AI(analog signal input)

Analog signal input, 3 channels, device like water detector

DO(digital signal output)

Dry-connector type output, 2 channels

Reset key

>5s press, recovery to default

RJ45

10/100Base-TX

Air-conditioner

Power input

220VAC

Control signal

RS485

Dimension

750*450*200mm

Cooling power

1500W

Heater power

1000W

Cooling fan

Cooling fan

4 sets, DC12V, temperature-controlled

Illustration LED

Illustration LED

2 sets, AC220V, turn on when door open

Smoke detector

Smoke detector

1 sets, DC12V

Water detector

Water detector

1 sets

Heater

Heater

4 sets(if Air-conditioner has heater, do not need it), AC220V 200W

Temperature humidity detector

Temperature humidity detector

Environment and power controller inside

IP camera

IP camera

1 sets, DC12V, using for taking a picture when door open and monitoring internal space of cabinet

PDU

PDU

10 digit PDU cabinet socket, new national standard 5-hole 10A

 

 

 

 


cabinet NPBHZA03.png